Using the ClimateMaster Service Tool When Replacing a DXM/CXM Board
Replacing a DXM control board requires more than simply swapping hardware. Proper configuration and verification are critical to ensure the unit operates correctly after installation. The ClimateMaster Wireless Service Tool (WST) makes the process faster and more accurate by allowing technicians to configure, verify, and test the new board directly from a phone or tablet.

This guide outlines the basic process for using the service tool during a DXM/CXM board replacement.
Step 1: Install the New DXM Board
Disconnect power to the unit.
Remove the failed DXM board.
Install the replacement board and reconnect wiring according to unit documentation.
Restore power to the unit.
Before continuing, verify the board powers up correctly and no immediate faults are present.
Step 2: Connect the Wireless Service Tool
Plug the Wireless Service Tool into the DXM communication port using the correct harness.
Confirm the tool’s Power LED turns on.
Verify TX/RX lights are flashing, indicating communication with the board.
The tool can be powered directly from the unit or via USB-C if needed.
Step 3: Connect Your Device
Open Wi-Fi settings on your phone or tablet.
Connect to the WST network (WSTXXX).
Enter the password: 12345678 (unless otherwise set)
Open a browser and navigate to:
192.168.4.1 (if the interface does not load automatically).
Step 4: Verify Unit Configuration
After replacing a DXM board, configuration settings may not match the unit requirements. This is the most important step.
In the WST Web App:
Go to Settings.
Verify or update:
Unit configuration
Blower configuration
Loop configuration
Option settings
Unit size and family
Always reference the unit’s model information and documentation to confirm proper setup.
Step 5: Check Diagnostics
Navigate to Diagnostics and confirm:
Control voltage is stable
Compressor and blower status are normal
Inputs and outputs are responding correctly
No active lockouts or faults
This step helps confirm wiring and settings were transferred correctly during installation.
Step 6: Run Manual Operation / Test Mode
Use Manual Operation to verify equipment response:
Enter test mode
Activate heating or cooling calls
Adjust airflow if needed
Confirm compressor and fan operation
This allows you to verify operation without waiting for thermostat calls.
Step 7: Review Fault History
Check Fault History to ensure no recurring issues are present after startup.
If faults appear immediately after replacement, revisit configuration and wiring before leaving the site.
Step 8: Generate a Startup Report (Recommended)
For documentation and quality assurance:
Go to Reporting.
Generate a startup report.
Save or export data as needed.
This provides a record of operating conditions after the board replacement.
Step 9: Final Checks Before Leaving the Jobsite
Confirm stable operation in heating and cooling modes.
Verify airflow and loop operation.
Ensure no active alarms or lockouts.
Disconnect the service tool and reinstall access panels.
Common Mistakes to Avoid
Skipping unit configuration after board replacement
Leaving default settings unchanged
Not verifying airflow settings
Forgetting to run test mode before leaving
The service tool helps prevent these issues by allowing quick confirmation of all major parameters.
Bottom Line
Using the ClimateMaster Wireless Service Tool when replacing a DXM board ensures the new control is configured correctly, operating safely, and fully tested before startup is complete. It reduces callbacks, speeds troubleshooting, and helps standardize service procedures across technicians.